Products

NAYY-J -O Al PVC PVC 0.6/1KV POWER CABLE

APPLICATIONS OVERVIEW

NAYY is preferentially used in outdoor applications, for indoor installations, in the open air,underground and in water where mechanical damage is not anticipated.

NAYY -J -O AL PVC PVC 0.6/1KV POWER CABLE

NAYY -J -O AL PVC PVC 0.6/1KV POWER CABLE APPLICATION

The NAYY -J is a power and control cable designed for fixed installation. It can be safely deployed in most applications where mechanical stresses are not anticipated – indoors, outdoors, direct burial underground, in concrete, or submerged in water. It is not suitable for installation in concrete which is shaken, vibrated, or compressed.

Available in sizes up to 27 core, the NAYY -J is available with an RE Class 1 solid copper conductor or an RM Class 2 stranded copper conductor.

The cable is sheathed in Flame-Retardant Polyvinyl Chloride (FR-PVC), has a voltage rating (U0/U) of 600/1000V, and an operating temperature range of -15oC to +70oC when fixed and -5oc to +50oC when flexed.

NAYY -J -O AL PVC PVC 0.6/1KV POWER CABLE CONSTRUCTION:

NAYY-J -O Al PVC PVC 0.6 1KV POWER CABLE Construction

– Single or multiple Aluminum

– Solid strand to VDE-0295 Class-1 – For #4 AWG and up, VDE-0295 Class-2 strand

– PVC core insulation – Color code to VDE-0293-308 with ground – Above 5 cores, color is black w/ white numbers

– PVC (DMV5) outer jacket – Black (RAL 9005)

NAYY -J -O AL PVC PVC 0.6/1KV POWER CABLE TECHNICALS:

– Working voltage: 600/1000 volts

– Test voltage: 4000 volts

– Flexing bending radius: 15 x Ø

– Static bending radius: 12 x Ø

– Flexing temp: -5º C to +50º C

– Static temp: -40º C to +70º C

– Flame retardant: IEC 60332.1

– Insulation resistance: > 100 MΩ x km

Conductor Inductance Current – Carrying

Capacity at 30° C *

Short circuit

current at 1 sec

Nom. Cross

Section Area

DC Resistance

at 20°C

AC Resistance

at 70°C

in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.701 0.269 53 59 0.76
16 1.91 2.295 0.253 71 77 1.22
25 1.20 1.442 0.257 93 99 1.90
35 0.868 1.043 0.247 115 119 2.66
50 0.641 0.770 0.247 134 135 3.80
70 0.443 0.533 0.238 167 165 5.32
95 0.320 0.385 0.238 207 198 7.22
120 0.253 0.305 0.233 240 225 9.12
150 0.206 0.248 0.235 277 254 11.40
185 0.164 0.198 0.233 316 286 14.06
240 0.125 0.152 0.232 377 332 18.24
300 0.100 0.122 0.231 433 376 22.80

NAYY -J -O AL PVC PVC 0.6/1KV POWER CABLE Specification

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×25 re 13.0 200
1×50 rm 16.5 310
1×70 rm 18.5 400
1×95 rm 21.0 520
1×120 rm 22.5 600
1×150 rm 23.5 700
1×185 rm 25.5 870
1×240 rm 28.5 1090
1×300 rm 31.5 1335
1×400 rm 35.5 1685
1×500 rm 39.0 2075
1×630 rm 43.0 2540
4×25 re 27.0 1000
4×35 re 29.0 1200
4×50 se 30.5 1350
4×70 se 34.5 1750
4×120 se 42.5 2630
4×150 se 45.5 3000
4×185 se 50.5 3780
4×240 se 54.0 4740
4G25 re 27.0 1000
4G35 re 29.0 1200
4G50 se 30.5 1350
4G70 se 34.5 1750
4G95 se 38.5 2250
4G120 se 42.5 2750
4G150 se 45.5 3200
4G185 se 50.5 3950
4G240 se 54.0 4700
4G240 sm 55.5 4960
4G150 se+1×1.5 re 45.5 3010
4G150 se+2×1.5 re 45.5 3020

DISCLAIMER: This is just part of the standard parameters of our products. Please contact our Engineer if you need more. And the information contained within this webpage is for guidance only and is subject to change without notice or liability. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All pictures shown are for illustration purposes only. The actual product may vary. All the information is provided in good faith and is believed to be correct at the time of publication.

Reviews

There are no reviews yet.

Be the first to review “NAYY-J -O Al PVC PVC 0.6/1KV POWER CABLE”