Products

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV

APPLICATION PREVIEW
A low smoke zero halogen, flame retardant power cable. For fixed indoor and outdoor installations as well as in concrete, but not for direct burial in ground or application in water.

Category: Tags: , , ,

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV APPLICATION

N2XCH is suitable for fixed installation in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Not intended for direct laying in ground or water. For outdoor application can be laid in tubes, but in that case should be taken all precautionary measures necessary to prevent water penetration into the tubes.

N2XCH is also suitable for supply systems in an emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar.

N2XCH concentric conductor serves as electromagnetic screen, which could be applied as neutral conductor too.

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV CABLE CONSTRUCTION

Conductor Bare copper, solid or stranded, IEC 60228, EN 60228, (VDE 0295)
Insulation Cross-linked Polyethylene, CENELEC HD 604 S1, VDE 0276-604
Filler Halogen-free compound or plastic tape
Concentric conductor Bare copper wires with reinforced helix
Separator Plastic tape
Outer sheath Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 “HM4”
Core colours CENELEC HD 308 S2 and VDE 0293
Sheath colour Black

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV PROPERITES

Halogen-free, no liberation of corrosive or toxic gases
Limited propagation of fire
Low smoke development
The materials used in manufacture are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
Flame test to DIN VDE 0482 part 266-2, BS 4066 part 3 / DIN EN 50266-2 / IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C)
Corrosiveness of combustion gases according to VDE 0482 part 267 / DIN EN 50267-2-2 / IEC 60754-2 (equivalent DIN VDE 0472 part 813)
Halogen-free according to DIN VDE 0482 part 267 / DIN EN 50267-2-1 / IEC 60754-1 (equivalent DIN VDE 0472 part 815)
Smoke density according to VDE 0482 part 1034-1+2 / IEC 61034-1+2 / DIN EN 61034-1+2 / BS 7622 part 1+2 (equivalent DIN VDE 0472 part 816)
Note
RM = round conductor, multiple-wire
RE = round conductor, single-wire

ADVANTAGES
– halogen-free, no release of toxic or corrosive gases under fire
– reduced smoke occurrence under fire
– no flame propagation in vertical cable bundle

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV TECHNICAL DATA

Power and control cable according to DIN VDE 0276 part 604, HD 604 S1 part 1 and part 5G
Conductor Resistance (at +20°C/+68°F)
According to VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2 and HD 383 cl. 1 and cl. 2
Temperature Range
During Installation
-5°C to +50°C (+23°F to +122°F)
For Fixed Installation
-30°C to +90°C (-22°F to +194°F)
Permissible Operating Temperature
at conductor +90°C/+194°F
Nominal Voltage U0/U 0.6/1 kV
Test Voltage 4 kV
Minimum Bending Radius
Single-conductor approx. 15x cable Ø
Multi-conductor approx. 12x cable Ø
Radiation Resistance
Up to 100×106 cJ/kg (up to 100 Mrad)

N2XCH XLPE Screened LSZH Power Cable 0.6/1KV SPECIFICATION

Number of cores and

mm² per conductor

Outer diameter

(mm)

Copper index

(kg/km)

Weight

(kg/km)

2×1,5 RE/1,5 11,1 52 172
2×2,5 RE/2,5 11,9 80 213
2×4 RE/4 14 122 322
2×6 RE/6 15 183 410
2×10 RE/10 17 311 550
2×16 RM/16 19 490 790
3×1,5 RE/1,5 11,5 66 190
3×2,5 RE/2,5 12,3 103 239
3×4 RE/4 13,5 160 314
3×6 RE/6 14,9 242 410
3×10 RE/10 16,8 408 600
3×16 RM/16 19,9 643 896
3×25 RM/16 25,3 1001 1360
3×35 RM/16 29,2 1400 1795
3×50 RM/25 32 2003 2460
3×70 RM/35 36 2794 3080
3×95 RM/50 39 3790 4310
3×120 RM/70 42 4785 5233
3×150 RM/70 44 5100 5788
3×185 RM/95 48 6381 7150
3×240 RM/120 54 8240 9273
4×1,5 RE/1,5 12,2 81 217
4×2,5 RE/2,5 13,2 129 275
4×4 RE/4 14,5 202 365
4×6 RE/6 15,9 296 479
4×10 RE/10 18 504 709
4×16 RM/16 21,5 796 1068
4×25 RM/16 25,6 1142 1526
4×35 RM/16 26,9 1526 1814
4×50 RM/25 29,6 2203 2405
4×70 RM/35 34 3082 3378
4×95 RM/50 38,5 4208 4568
4×120 RM/70 42,7 5388 5773
4×150 RM/70 46,6 6540 6921
4×185 RM/95 51,8 8195 8866
4×240 RM/120 57,6 10546 11167
7×1,5 RE/1,5 15 133 380
7×2,5 RE/2,5 15 200 378
7×4 RE/4 18 315 599
7×6 RE/6 19 470 850
10×1,5 RE/2,5 17,2 177 420
10×2,5 RE/4 18,9 287 550
12×1,5 RE/2,5 17,2 205 437
12×2,5 RE/4 19 334 589
12×4 RE/6 23 528 920
16×1,5 RE/4 20 275 686
16×2,5 RE/6 20,9 450 805
24×1,5 RE/6 22,7 413 764
24×2,5 RE/10 26 695 1189
30×1,5 RE/6 23,9 499 880
30×2,5 RE/10 26,6 840 1238

Additional information

standards

VDE 0276

Reviews

There are no reviews yet.

Be the first to review “N2XCH XLPE Screened LSZH Power Cable 0.6/1KV”

Your email address will not be published. Required fields are marked *