N2XCH XLPE Screened LSZH Power Cable 0.6/1KV
N2XCH XLPE Screened LSZH Power Cable 0.6/1KV APPLICATION
N2XCH is suitable for fixed installation in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Not intended for direct laying in ground or water. For outdoor application can be laid in tubes, but in that case should be taken all precautionary measures necessary to prevent water penetration into the tubes.
N2XCH is also suitable for supply systems in an emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar.
N2XCH concentric conductor serves as electromagnetic screen, which could be applied as neutral conductor too.
N2XCH XLPE Screened LSZH Power Cable 0.6/1KV CABLE CONSTRUCTION
Conductor | Bare copper, solid or stranded, IEC 60228, EN 60228, (VDE 0295) |
Insulation | Cross-linked Polyethylene, CENELEC HD 604 S1, VDE 0276-604 |
Filler | Halogen-free compound or plastic tape |
Concentric conductor | Bare copper wires with reinforced helix |
Separator | Plastic tape |
Outer sheath | Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 “HM4” |
Core colours | CENELEC HD 308 S2 and VDE 0293 |
Sheath colour | Black |
N2XCH XLPE Screened LSZH Power Cable 0.6/1KV PROPERITES
Halogen-free, no liberation of corrosive or toxic gases
Limited propagation of fire
Low smoke development
The materials used in manufacture are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
Flame test to DIN VDE 0482 part 266-2, BS 4066 part 3 / DIN EN 50266-2 / IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C)
Corrosiveness of combustion gases according to VDE 0482 part 267 / DIN EN 50267-2-2 / IEC 60754-2 (equivalent DIN VDE 0472 part 813)
Halogen-free according to DIN VDE 0482 part 267 / DIN EN 50267-2-1 / IEC 60754-1 (equivalent DIN VDE 0472 part 815)
Smoke density according to VDE 0482 part 1034-1+2 / IEC 61034-1+2 / DIN EN 61034-1+2 / BS 7622 part 1+2 (equivalent DIN VDE 0472 part 816)
Note
RM = round conductor, multiple-wire
RE = round conductor, single-wire
ADVANTAGES
– halogen-free, no release of toxic or corrosive gases under fire
– reduced smoke occurrence under fire
– no flame propagation in vertical cable bundle
N2XCH XLPE Screened LSZH Power Cable 0.6/1KV TECHNICAL DATA
Power and control cable according to DIN VDE 0276 part 604, HD 604 S1 part 1 and part 5G
Conductor Resistance (at +20°C/+68°F)
According to VDE 0295 cl. 1 or 2 and IEC 60228 cl. 1 or 2 and HD 383 cl. 1 and cl. 2
Temperature Range
During Installation
-5°C to +50°C (+23°F to +122°F)
For Fixed Installation
-30°C to +90°C (-22°F to +194°F)
Permissible Operating Temperature
at conductor +90°C/+194°F
Nominal Voltage U0/U 0.6/1 kV
Test Voltage 4 kV
Minimum Bending Radius
Single-conductor approx. 15x cable Ø
Multi-conductor approx. 12x cable Ø
Radiation Resistance
Up to 100×106 cJ/kg (up to 100 Mrad)
N2XCH XLPE Screened LSZH Power Cable 0.6/1KV SPECIFICATION
Number of cores and
mm² per conductor |
Outer diameter
(mm) |
Copper index
(kg/km) |
Weight
(kg/km) |
2×1,5 RE/1,5 | 11,1 | 52 | 172 |
2×2,5 RE/2,5 | 11,9 | 80 | 213 |
2×4 RE/4 | 14 | 122 | 322 |
2×6 RE/6 | 15 | 183 | 410 |
2×10 RE/10 | 17 | 311 | 550 |
2×16 RM/16 | 19 | 490 | 790 |
3×1,5 RE/1,5 | 11,5 | 66 | 190 |
3×2,5 RE/2,5 | 12,3 | 103 | 239 |
3×4 RE/4 | 13,5 | 160 | 314 |
3×6 RE/6 | 14,9 | 242 | 410 |
3×10 RE/10 | 16,8 | 408 | 600 |
3×16 RM/16 | 19,9 | 643 | 896 |
3×25 RM/16 | 25,3 | 1001 | 1360 |
3×35 RM/16 | 29,2 | 1400 | 1795 |
3×50 RM/25 | 32 | 2003 | 2460 |
3×70 RM/35 | 36 | 2794 | 3080 |
3×95 RM/50 | 39 | 3790 | 4310 |
3×120 RM/70 | 42 | 4785 | 5233 |
3×150 RM/70 | 44 | 5100 | 5788 |
3×185 RM/95 | 48 | 6381 | 7150 |
3×240 RM/120 | 54 | 8240 | 9273 |
4×1,5 RE/1,5 | 12,2 | 81 | 217 |
4×2,5 RE/2,5 | 13,2 | 129 | 275 |
4×4 RE/4 | 14,5 | 202 | 365 |
4×6 RE/6 | 15,9 | 296 | 479 |
4×10 RE/10 | 18 | 504 | 709 |
4×16 RM/16 | 21,5 | 796 | 1068 |
4×25 RM/16 | 25,6 | 1142 | 1526 |
4×35 RM/16 | 26,9 | 1526 | 1814 |
4×50 RM/25 | 29,6 | 2203 | 2405 |
4×70 RM/35 | 34 | 3082 | 3378 |
4×95 RM/50 | 38,5 | 4208 | 4568 |
4×120 RM/70 | 42,7 | 5388 | 5773 |
4×150 RM/70 | 46,6 | 6540 | 6921 |
4×185 RM/95 | 51,8 | 8195 | 8866 |
4×240 RM/120 | 57,6 | 10546 | 11167 |
7×1,5 RE/1,5 | 15 | 133 | 380 |
7×2,5 RE/2,5 | 15 | 200 | 378 |
7×4 RE/4 | 18 | 315 | 599 |
7×6 RE/6 | 19 | 470 | 850 |
10×1,5 RE/2,5 | 17,2 | 177 | 420 |
10×2,5 RE/4 | 18,9 | 287 | 550 |
12×1,5 RE/2,5 | 17,2 | 205 | 437 |
12×2,5 RE/4 | 19 | 334 | 589 |
12×4 RE/6 | 23 | 528 | 920 |
16×1,5 RE/4 | 20 | 275 | 686 |
16×2,5 RE/6 | 20,9 | 450 | 805 |
24×1,5 RE/6 | 22,7 | 413 | 764 |
24×2,5 RE/10 | 26 | 695 | 1189 |
30×1,5 RE/6 | 23,9 | 499 | 880 |
30×2,5 RE/10 | 26,6 | 840 | 1238 |
Reviews